6 MW (6,000 kW) Combined Standby / Prime Power Block. Low-Hour MTU Series 4000 Engines, Medium Voltage (13.2kV), Outdoor Attenuated Enclosures, and Utility-Grade Paralleling Switchgear.

Complete System Overview
Up for sale is a complete, utility-grade 6 Megawatt power plant block consisting of (3) matched 2,000 kW MTU / Detroit Diesel Medium Voltage generator sets. The package is turnkey-ready, featuring custom sound-attenuated outdoor enclosures built by Enercon Engineering and complete multi-breaker outdoor paralleling switchgear with protection relays and utility interties. Full drawing packages (including Enercon drawing DE-35136) and electrical schematics are included.

Generator Set Specifications (Per Unit / Total 3 Units)
Generator Model: Detroit Diesel / MTU 2000DSEB

Serial Numbers: 2054270 (and matched pair)

Standby Rating: 2,000 kW (2,500 kVA @ 0.8 PF)

Combined Block Capacity: 6,000 kW (7,500 kVA)

Voltage Output: 7,620 / 13,200 Volts (Medium Voltage, 3-Phase, 4-Wire)

Frequency & Speed: 60 Hz @ 1,800 RPM

Generator End / Alternator: Marathon 10M5582 (Insulation NEMA Class F / 40°C Ambient)

Operating Hours: Extremely Low-Hour Units (~703 Total Run Hours)

Controller / Digital Panel: Kohler / MTU DEC 550 Digital Controller (24V DC, 10A SPDT Dry Contact Array)

Engine Specifications
Engine Manufacturer: Detroit Diesel / MTU

Engine Series: Series 4000 MDEC (Model 16V4000)

Displacement: 65.0 Liters (V16 Configuration)

Power Output: 2,937 HP (2,198 kW) @ 1,800 RPM

Fuel System & Injection: Electronic Common Rail Injection (MDEC Engine Management)

Injection Timing: Initial Injection Timing 12 Deg. BTC

Fuel Rate: 613.0 mm³/stroke at advertised kW

Emissions Rating: EPA Non-Road Tier 1 (2005 U.S. EPA & California Non-Road Certified)

Cooling System: Unit Mid-Radiator Assembly with Heavy-Duty Belt Driven Fan

Switchgear & Control Protection System
Manufacturer / Integration: Utility-Grade Paralleling Switchgear Package

Protection Relays: Integrated Basler Electric BE1-11 Protection Systems & GE Static Timing Relays (62-1)

Power Monitoring: Digital Multi-Function Power Meters & HMI Display Panels

Utility Controls: Dedicated Utility Intertie Breaker Control, Auto/Manual Sync, System Alarm/Annunciator Arrays

Enclosures & Sub-Base Fuel System
Enclosure Builder: Enercon Engineering, Inc. (Drawing No. DE-35136)

Type: Heavy-Duty Sound-Attenuated Weatherproof Walk-In Enclosures with Snow-Hood Intakes & Service Access Doors

Dimensions (Per Enclosure): 334.00" L × 120.06" W × 111.93" H (Approx. 27.8 ft L × 10 ft W)

Base: Heavy-Duty Steel Skid with Integrated Sub-Base Fuel Tank and Extension Shipping Skid Extensions

Target Applications: International Power Projects, Remote Mining & Extraction, Offshore/Coastal Installations, Heavy Agricultural Cooperatives, Unregulated Global Microgrids, or Standby Emergency Power Backup.

Status: Low hours, well-maintained, complete engineering package on hand. Ready for loading and global export.